0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR POWER CABLES
                
            
0,6/1 kV PVC INSULATED WITH ALUMINUM CONDUCTOR POWER CABLES
| Code | YAVV-R (TSE), NAYY (VDE), AL/PVC/PVC (BS) | 
| Standarts | TS IEC 60502-1, VDE 0276 | 
| Construction | Aluminum Conductor, PVC insulated, PVC Outer Sheath | 
| Application | Used in excessive mechanical stresses on internal-external ground and in the cable channel as Lightning and power cable. | 
| Technical Datas | Max. Operating Temp.  70 °C Max. Short Circuit Temp. Cross S. ≤ 300 mm² 160°C Cross S. >300 mm² 140°C Min. Bending Radius 12*D D:Cable Overall Diameter (mm) | 
- Product Description
| Dimensions and Weights | Electrical Information | |||||
| Nominal cross-section | Overall Diameter | Net weight | Delivery reel size for 1000 m cable | Conductor DC (max.) resistance at 20 °C (max.) | Current carrying capacity (approx.) | |
| (mm²) | (mm) | (kg/km) | (cm) | (ohm/km) | Ground (A) at 20°C | Air (A) at 30°C | 
| 4x25 rm | 26,0 | 900 | 140 | 1,200 | 99 | 83 | 
| 4x35 rm | 29,0 | 1100 | 150 | 0,868 | 118 | 102 | 
| 4x50 rm | 33,0 | 1520 | 160 | 0,641 | 142 | 124 | 
| 4x70 rm | 37,0 | 1900 | 200 | 0,443 | 176 | 158 | 
| 4x95 rm | 42,0 | 2500 | 220 | 0,320 | 211 | 190 | 
| 4x120 rm | 46,0 | 3050 | 230 | 0,253 | 242 | 221 | 
| 4x150 rm | 51,0 | 3900 | 240 | 0,206 | 270 | 252 | 
| 4x185 rm | 56,0 | 4600 | 210* | 0,164 | 308 | 289 | 
| 4x240 rm | 64,0 | 5900 | 230* | 0,125 | 363 | 339 | 
| 4x300 rm | 71,0 | 7250 | 230* | 0,100 | 412 | 377 | 
| 4x400 rm | 79,0 | 9500 | 240* | 0,0778 | 475 | 444 | 